Toshiba offers precise network control of new VRF systems in both standalone applications for autonomous monitoring of the air conditioning system, and integrated into a central control scheme together with Super Digital Inverter and Digital Inverter split systems.
The innovative solutions of the Toshiba Network guarantee maximised integration with other building systems such as elevators, fire protection systems, lighting etc. Open-network controls are specifically designed for Building Management Systems.
Technical Data
Wide Toshiba VRF Control Applications (TCC-Link Controls)
1. Touch-screen controller and Toshiba central remote controller
2. WEB-based controller
Description
Toshiba offers precise network control of new VRF systems in both standalone applications for autonomous monitoring of the air conditioning system, and integrated into a central control scheme together with Toshiba Super Digital Inverter and Digital Inverter split systems.
The innovative solutions of the Toshiba Network guarantee maximised integration with other building systems such as elevators, fire protection systems, lighting etc. Open-network controls are specifically designed for Building Management Systems.
Contact Toshiba Vietnam: +84 4 665 88886 for more support.
Compliant manager BMS-CM1280FTLE
Individual operation of 128 indoor units available. Zone setting (64 zones x 2).
WEB function (Intranet)
Energy monitoring
Easy settings and operations, 10 times per day/ 32 times per week:
on/off ,
operating mode,
setting temperature,
remote control restriction
TCC-Link direct connection
Password available
Schedule timer
Web Application (BMS-CM1280FTLE): error history electrical power distribution external connection (PC is necessary).
Using the touch-screen controller provides a clear display and enables easy operation. A maximum of512 units are controllable using the one-touch controller.
Energy monitoring and billing application. Power meter interface, power meter locally supplied Energy Monitoring relay I/F (BMSIFWH4E2)
Power Meter (Local Supply) 1 kWh/pulse or 10 kWh/pulse (Pulse duration 50 to 1000 ms) (Maximum 8 power meter per interface).
WEB Based Controller BMS-WE01GTE (WEB Server), BMS-WB2561PWE (Gateway Server)
Signals and provides the following functions :
Operation monitoring
Operation control
Operation Schedule
Operation display
Error Code
Alarm List
Energy monitoring/Billing
Digital I/O Signal Control
Connect the WEB server for every 256 indoor units, and connect a gateway server upstream from the server.
Relay Interface:
BMS-IFWH4E2 for Energy Monitoring
BMS-IFDD02E2 for Digital I/O
BMS-IFLSV3E for TCS-NET
Intelligent Server BMS-LSV6E
The BACnet® system operates in conjunction with the BAC net server. Server uses object signals to provide the following functions:
Object signals command:
ON/OFF
Mode: cool/heat/fan
Temperature setting
Central/local
Fan speed
Monitoring:
ON/OFF etc.
Mode:
Cool/heat/fan/failure
Temperature setting
Room temperature
Central/local
Energy monitoring, etc.
LonWorks Gateway TCB-IFLN640TLE2
LonWorks® LN Interface
The LonWorks® interface manages the Toshiba SMMS air conditioning system as a Lon device to communicate with the custormer’s Building Management System and to monitor operational status. A maximum of 64 units are controllable per interface.
Mode – Cool/heat/fan/failure – Temperature setting – Room temperature – Central/local, etc.
Modbus Interface TCB-IFMB640TLE
The Modbus® interface manages the SMMS air conditioning system as a Modbus® device to communicate with the custormer’s Building Management System. Accessible to 64 units per one TCB-IFMB640TLE, 15 TCBIFMB640TLE on one Modbus Master (prepared by user).
Signals and provides the following functions:
ON/OFF
Mode: cool/heat/fan
Air flow/Louver setting
Temperature setting
Filter reset
Accumulated operation time, etc.
All information on the Site (the "Information") is copyrighted by Toshiba Vietnam and protected by law. Write "www.ToshibaVietnam.Vn" when release the information from this website. - Contact +84 4 665 88886 for more support!
Toshiba Air Conditioners - 2-way Cassette Indoor Unit, VRF
"Invisible" Toshiba unit
With its very compact size, this two-way cassette unit for VRF s...
Toshiba Air Conditioners - High-wall Indoor Unit (3 series), VRF
With its modern slim-line design and elegant "moon white" color, NEW high-wall unit To...
Toshiba Air Conditioners - Ducted High Pressure Indoor Unit, VRF
Key Features of Concealed Duct High Static Pressure Type
This is Toshiba’s most power...
Toshiba SHRM key features
The three-pipe VRF Super Heat Recovery Multi System (SHRM) delivers simultaneously cooling and heating and has exceptional energy efficiency. T...
Product information on this site may have been sourced from overseas suppliers/entities and has not been created by Toshiba Vietnam, therefore, Toshiba Vietnam does not necessarily warrant the accuracy of the content and/or detail of such information. To the extent permitted by law, Toshiba Vietnam is not liable for any errors, omissions or misrepresentations in such information or for any loss or damage suffered by persons who use or rely on the information.